Class ChangeĪ pair of unmonitored terminals allow only the system alarm sounders to be actuated from a remote position. The auxiliary circuits should be powered from an independent power supply. These are normally open (NO) and normally closed (NC) contacts that switch over when the panel goes into a fire condition.ġA for a resistive load and should not be used to switch voltages in excess of 50V.

gent 3260 installation manual

GENT Xenex fire panels Auxiliary Contacts Where a sounder circuit is not being used, the end-of-line resistor must be fitted across its terminals in the control panel. It is important that the last alarm sounder is fitted with a 22K The alarm sounder circuits are regularly pulse monitored for failure. The load must be shared between the sounder circuits. To comply with the requirements of BS 5839: Part 1:1988, a minimum of two alarm sounder circuits should be used on all installations. (sectors) will always operate together in the event of a fire condition. GENT Xenex fire panels NOTE: All sounder circuits Where a zone circuit is not being used, the end-of-line capacitor unit must be fitted across its terminals in the panel. Used, then it must be powered from an independent supply.

#Gent 3260 installation manual manual

An end-of-line capacitor unit is required for zone circuit monitoring, which must be fitted after the last detector or manual call point on the circuit.Īll manual call points used must have a 470 ohms series resistor. System design Fire Detection (Zone Circuits)ĢmA load. Supply will affect the panel standby capability. The power supply terminals ‘24+ and 0’ may drive external ancillary equipment and is designed to be used in conjunction with auxiliary contacts and common fire and fault outputs, see control panel With the recommended battery the control panel will provide a standby supply under mains failure conditions, for a period ofħ2 hours followed by 30 minutes of alarm load, see specification. The mains supply to the control panel should be via a fused spur unit rated: Practice for system design installation and servicing. The design of the fire detection and alarm system should be to See control panel specification sounder circuit loading.Ĥ5mA NOTE: The door holder circuit should be controlled by the control panel’s auxiliary contacts, using external Maximum can be upto 65mA limited by the control panel n/a n/aĪs per detectors NOTE: If the beam detector is used then it must be powered from an external power supply. See control panel specification for zone circuit loading. Specifications GENT Xenex fire panels Zone circuit products (24Vdc) Test, Power, Access/Function (Yellow LEDs ‘lights’)Ī maximum of up to 6 repeat panels connected in series to the control panel ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, NOTE: Only a limited number of functions are accessible at the

#Gent 3260 installation manual serial

Serial port, see also repeat panel specificationīS EN50130-4: 1995: Part 4 Alarm systems : Electromagnetic compatibility Product family standard: Immunity requirements forĬomponents of fire, intruder and social alarm systems

gent 3260 installation manual

ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power, (via piezoelectric buzzer operating at 2KHz 70dB(A) at 1m) Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric keypad.įire & System Fault - continuous sound Fault - intermittent sound Normally open push button, up to 100m cable distance away from the panelġ00mA maximum at 24V d.c. Open collector - normally Off (with 1K ohms limiting resistor) Open collector - normally On (with 1K ohms limiting resistor) Pair of normally closed (NC) and a pair of normally open (NO) contacts ratedġA 24V dc resistive load (Maximum 100m cable distance)

#Gent 3260 installation manual code

(AL1 Authorised user - No code is required) User access: By means of code entry via numeric key pad Product family standard: Immunity requirements for components of fire, intruder and social alarm systemsīattery standby with 1mA load per zone and 1A total sounder alarm load Zone circuit: Capacitor (diode) unit Sounder circuit: 22K ohms resistorīS EN50081-1:1992: Part 1 Residential, Commercial & Light industryīS EN50130-4: 1995: Part 4 Alarm systems : Electromagnetic compatibility

gent 3260 installation manual

GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat panels These instructions must be left on site with the person responsible for the fire alarm system.įigure 1 Fire alarm control / repeat panel